ARCT-B — Block Type (Support) Current Transformer
Instrument Transformers

ARCT-B — Block Type (Support) Current Transformer

Cast-resin support-type current transformer for medium-voltage cells — measurement, metering and relay protection.

12 / 24 / 36 kVup to 3,000 A60 kA
Request a Quote →

ARCT-B12/B24/B36 block-type current transformers are installed in switchgear cells and additionally serve as a support insulator. 1–3 secondary windings per phase; accuracy class and burden per specification.

Technical Specifications

ParameterARCT-B12ARCT-B24ARCT-B36
Maximum operating voltage (Um)12 kV24 kV36 kV
Test voltages28 / 75 kV50 / 125 kV70 / 170 kV
Maximum rated primary current2,500 A3,000 A3,000 A
Rated secondary current1 or 5 A1 or 5 A1 or 5 A
Short-time thermal currentUp to 60 kA (1,000 × In)
Rated dynamic currentUp to 120 kA (2.5 × Ith)
Weight20–35 kg33–50 kg45–60 kg

Request a Quote

We reply within one business day. Your data is used only to prepare the quotation.