SF₆ Gas Insulated Circuit Breaker
MV Components

SF₆ Gas Insulated Circuit Breaker

Medium-voltage circuit breaker with SF₆ as the interrupting medium. M1/E2 endurance classes, peak withstand up to 50 kA.

12–36 kV630–1250 AM1 / E2
Request a Quote →

The SF₆ circuit breakers are used in switchgear cells for switching load currents and interrupting short-circuit currents. Fast arc quenching in SF₆ ensures minimal contact wear and easy maintenance.

Technical Specifications

Parameter12–24 kV36 kV
Rated voltage12/24 kV36 kV
Rated current630–1250 A630–1250 A
Lightning impulse withstand voltage125 kV170 kV
Power frequency withstand voltage50 kV70 kV
Short-circuit withstand current (3 s)16–20 kA16–20 kA
Rated peak short-circuit withstand40–50 kA40–50 kA
Mechanical endurance classM1M1
Electrical endurance classE2E2
Interrupting mediumSF₆SF₆

Request a Quote

We reply within one business day. Your data is used only to prepare the quotation.